Incident Report
Incorrect Relief Valve Set Point Leads to Explosion
No Incident Date defined.
Severity:
Incident
Was Hydrogen released?
Yes
Was there Ignition?
Yes
No Ignition Source Defined.
Description
Incident Synopsis
During a standard testing procedure, a 3,000 psig relief valve actuated at normal line pressure, releasing gaseous H2. The gaseous H2 combined with air, resulting in an explosion which damaged the test facility.
Cause
The relief valve was improperly set to open at line pressure, and the inspection was inadequate in that it didn't identify this error. Contributing cause was poor design of the venting system, which was installed in a horizontal position, causing inadequate venting and buildup of static electricity.
Setting
- Laboratory
Equipment
Piping/Fittings/Valves
- Valve
Ventilation System
- Venting System
Damage and Injuries
- Property Damage
Probable Cause(s)
- Improper Relief Valve Set Point
- Inadequate Venting Design
Contributing Factors
- Equipment Failure
- Design Flaw
- Inadequate Inspection
Characteristics
- High Pressure (> 100 bar)
The incident was discovered During Inspection.
Lessons Learned/Suggestions for Avoidance/Mitigation Steps Taken
The site needs to implement a good Operational and Readiness Inspection procedure. System inspection deficiencies need to be identified, and (if possible) reviewed by a second party before future tests are conducted. This inspection could include the following:
- Check all relief valve set points
- Check potential design flaws
- Check all other relevant operational characteristics
Date Added to H2Incidents: 2/7/2007

